Huawei SUN2000-63KTL-JPH0 User Manual page 51

Hide thumbs Also See for SUN2000-63KTL-JPH0:
Table of Contents

Advertisement

SUN2000-63KTL-JPH0
User Manual
Sufficient slack should be provided in the PE cable to ensure that the last cable bearing the
force is the PE cable when the AC output power cable bears pulling force due to force
majeure.
If the cable outer diameter does not match the rubber liner, the IP rating of the device may
be affected.
Do not route the cable with a crimped OT/DT terminal directly through the rubber liner in
case it damages the liner.
Ensure that the cable jacket is in the maintenance compartment.
Ensure that AC terminations are secured. Failure to do so may cause the SUN2000 to
malfunction or damage to its terminal block by issues such as overheating.
Do not adjust the cable when the sealing nut is tightened. Otherwise, the rubber liner may
shift, which affects the IP rating of the device.
Figure 5-8 Installing the AC output power cable
----End
Issue 04 (2019-06-30)
The cable colors shown in figures are for reference only. Select an appropriate cable according to the
local standards.
Copyright © Huawei Technologies Co., Ltd.
5 Electrical Connections
44