SUN2000-63KTL-JPH0
User Manual
Alarm
Alarm Name
ID
2032
Grid Loss
2033
Grid Undervoltage
2034
Grid Overvoltage
Issue 04 (2019-06-30)
Alarm
Cause
Severity
Major
Cause ID = 1
1. The power grid
experiences an outage.
2. The AC circuit is
disconnected or AC switch
is off.
Major
Cause ID = 1
The grid voltage is below the
lower threshold or the low
voltage duration has lasted for
more than the value specified
by LVRT.
Major
Cause ID = 1
The grid voltage exceeds the
higher threshold or the high
voltage duration has lasted for
more than the value specified
by HVRT.
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance
Measures
1. The alarm disappears
automatically after the
power grid recovers.
2. Check that the AC power
cable is connected and
that the AC switch is
ON.
1. If the alarm occurs
accidentally, the power
grid may be abnormal
temporarily. The
SUN2000 automatically
recovers after detecting
that the power grid
becomes normal.
2. If the alarm occurs
frequently, check
whether the power grid
voltage is within the
acceptable range. If no,
contact the local power
operator. If yes, modify
the power grid
undervoltage protection
threshold with the
consent of the local
power operator.
3. If the fault persists for a
long time, check the AC
circuit breaker and AC
output power cable.
1. Check whether the grid
connection voltage
exceeds the upper
threshold. If yes, contact
the local power operator.
2. If you have confirmed
that the grid connection
voltage exceeds the
upper threshold and
obtained the consent of
the local power operator,
modify the overvoltage
protection threshold.
3. Check that the peak grid
voltage does not exceed
the upper threshold.
107