3.2.4 Electrical protection standard (protection class)
▪ Units: IP class IPX4.
▪ Scroll compressors up to ZX51: IP21 according to IEC 34.
▪ Fan: IP44 according to IEC 34.
▪ Solenoid valve coils: IP65 according to DIN 43650.
3.2.5 Main fuses
WARNING
Isolating switch "On"! Danger of electric shock! Before changing the fuses,
turn off the isolating switch to de-energize the unit.
Follow the steps described hereunder to replace the main fuses:
Pull off the grip with a
screwdriver

Figure 20: Replacement of the fuses

Unit
ZXME020E to ZXME040E-TFD
ZXLE020E to ZXLE040E-TFD
ZXDE030E to ZXDE060E-TFD
ZXME050E to ZXME075E-TFD
ZXLE050E to ZXLE075E-TFD
ZXDE075E-TFD
ZXME020E to ZXME030E-PFJ
ZXLE020E to ZXLE030E-PFJ
ZXME040E-PFJ
Table 28: Main fuses sizes and range
3.3
Refrigeration piping connections
3.3.1 Refrigeration piping installation
WARNING
High pressure! Risk of personal injury! The units are pressurized with dry
air. Be careful when opening connections on a pressurized item.
WARNING
Low surface temperature! Danger of frostbite! The liquid line should be
insulated with 19 mm insulation thickness. Temperature could be as low as
–15°C.
32
Pull the grip again by
hand to open the fuse
holder
Fuse size
3 × Fuse 10×38
3 × Fuse 10×38
1 × Fuse 10×38
1 × Fuse 10×38
As the fuse holder is
open, the fuses can
be replaced
Fuse range
Ident number
12A
3200810
16A
3200821
20A
3200832
25A
3200843
C6.1.6/0117-1017/E