Parameter
Description
Probe 7
A19
configuration
Defrost probe
G12
selection
G17*
Defrost type
Interval between
G18
defrost cycles
Maximum duration
G19
of defrost
Duration of pulse
G20
defrost
Defrost
G21
termination
temperature
G22
Defrost delay time
Defrost interval
G23**
mode
Display during
G24***
defrost
Maximum display
G25
delay after defrost
G26
Drip time
Defrost at power-
G27
on
Workday defrost
G28
start 1
Workday defrost
G29
start 2
Workday defrost
G30
start 3
Workday defrost
G31
start 4
Workday defrost
G32
start 5
G33
Workday defrost
start 6
Holiday defrost
G34
start 1
Holiday defrost
G35
start 2
Holiday defrost
G36
start 3
Holiday defrost
G37
start 4
Holiday defrost
G38
start 5
Holiday defrost
G39
start 6
16
Factory settings /
Recommended settings / Comments
Range
0 = Not used = nu
Evaporator temp (NTC10K) = 5 = EPt
0 = Not used = nu
5 = Evaporator temperature sensor = EPt
0 = Electrical = EL; 1 = Hot gas defrost
(not available on ZX units) = in;
0 = Electrical = EL
2 = Natural defrost (pulse defrost) = PLS
0 to 120 hours range; adjust to individual
4 hours
requirements
0 to 255 minutes; adjust to individual
20 minutes
requirements
15 minutes
0 to G19
10°C
-40°C to 110°C
15 minutes
0 to 255 minutes
0 = nu = Not used; 1 = in = Interval;
0 = Not used = nu
2 = rtC = Real time clock
0 = dEF = Defrost;
1 = Set = Case temperature setpoint;
DEFROST "dEF"
2 = it = Case temperature value;
3 = rt = Standard operation
0 minute
0 to 255 minutes
1 minute
0 to 120 minutes
Avoids defrost after initial power up. If
"YES", the controller will decide on defrost
0 = NO
related parameters if a defrost sequence is
required after initial start-up
00:00 – 23:50 or nu = Not used
00:00
00:00 – 23:50 or nu = Not used
04:00
00:00 – 23:50 or nu = Not used
08:00
00:00 – 23:50 or nu = Not used
12:00
00:00 – 23:50 or nu = Not used
16:00
00:00 – 23:50 or nu = Not used
20:00
00:00 – 23:50 or nu = Not used
00:00
00:00 – 23:50 or nu = Not used
04:00
00:00 – 23:50 or nu = Not used
08:00
00:00 – 23:50 or nu = Not used
12:00
00:00 – 23:50 or nu = Not used
16:00
00:00 – 23:50 or nu = Not used
20:00
C6.1.6/0117-1017/E