Appendix 4: Parameter list level 1 (Pr1)
Legend
L1 = Parameter in Level 1 (without password)
L2 = Parameter in Level 2 (with password = 3 2 1)
N.V. = Parameter not accessible
NOTE: When changing parameters C01 (Cin), C02 (CoU) and C05 (CPb) a reset of the controller (interruption of power supply) is required.
Parameter
Description
C01
Compressor cut-in pressure setpoint
C02
Compressor cut-out pressure setpoint
C07
Refrigerant selection for regulation
C16
Digital compressor setpoint
C17
Proportional band for compressor regulation
C21
Cycle time for digital compressor
C24
Minimum capacity for digital compressor
C25
Maximum capacity for digital compressor
Low pressure alarm value (from serial number
D29
16EZ08855M onwards)
Condenser temperature setpoint when fan
E39
setpoint modulation is disabled
E46
Regulation band of variable fan
N01
Current minute
N02
Current hour
N03
Date of month
N04
Month
N05
Year
T18
Access to Pr2 level
Table 31: Parameters level 1
C6.1.6/0117-1017/E
Range
CoU to US; C02 to C04
LS to Cin; C03 to C01
R404A (0-404) - R507 (1-507)
R134a (2-134) - R22 (3-R22)
R407C (4-07C) - R407A (5-07A)
R407F (6-07F) - R448A (7-48A)
R449A (8-49A)
LS to US; C03 to C04
0.1 to 9.9 bar; 0.1 to 99.9 PSI;
1 to 999 KPA; 0.1°C to 25.5°C
10 to 40 sec
0 to PMA; 0 to C25
PMi to 100; C24 to 100
0 to 15 bar
-40°C to 110°C
0.1°C to 25.5°C
0 to 59
0 to 23
1 to 31
1 to 12
0 to 99
[0÷999]
ZXDE
ZXME
ZXLE
N.V.
L1
L1
L2
L1
L1
L1
L1
L1
L1
N.V.
N.V.
L1
N.V.
N.V.
L1
N.V.
N.V.
L1
N.V.
N.V.
L1
N.V.
N.V.
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1