2.10.2 Remote display CCM60
This device allows for remote monitoring and control of the XCM25D controller via cable. The CCM60
has the same interface as the XCM25D controller therefore the commands and symbols are identical.
The remote display shall be mounted on a vertical panel, in a 29 x 71 mm hole, and secured using
the special bracket supplied (see Figure 11).
The temperature range allowed for correct operation is 0°C to +60°C.
Avoid places subject to strong vibrations, corrosive gases, excessive dirt or humidity. Allow for air to
circulate through the cooling holes.
When front-mounted, the remote display is IP65 rated.

Figure 11: Remote display front panel mounting

The remote display is a proprietary bus of communication for Dixell HMI (x-rep, CCM60) interfaces.
There are two connection terminals on the back of the remote display (+ and -).
NOTE: Emerson recommends to use a shielded cable twisted pair 2 x 0.5mm².
The device must be connected to the VNR-terminal on the unit controller according to the polarity.
Figure 12 shows the VNR terminal on the unit controller.
VNR connection for
the remote display

Figure 12: VNR connection for the remote display

Before connecting cables make sure the power supply complies with the hardware requirements.
Separate the terminal cables from the power supply cables, the outputs and the power connections.