Emerson Copeland EazyCool ZXME020E Application Manuallines page 62

Outdoor condensing units
Hide thumbs Also See for Copeland EazyCool ZXME020E:
Table of Contents

Advertisement

Code Description
G39
Holiday defrost start 6
G40
First weekly holiday
G41
Second weekly holiday
Fans operating mode
cn = Parallel to compressor, off during defrost;
G42
on = Fans always on, only off during defrost;
cy = Parallel to compressor, on during defrost;
oy = Fans permanently in operation
G43
Fans stop temperature
Temperature differential avoiding short cycles
G44
of fans
G45
Fan On time
G46
Fan Off time
Room probe selection for evaporator fan
G47
management
G48
Maximum case temperature alarm threshold
G49
Minimum case temperature alarm threshold
G50
Case temperature alarm restart differential
G51
Case temperature alarm delay
G52
Exclusion of temperature alarm at start-up
G53
Maximum door open time before alarm
Maximum length for light when door switch is
G54
closed
G55
Fan delay after defrost
G56
Use the liquid line solenoid
H01
Current sensing 1
H02
Current sensing 2
C6.1.6/0117-1017/E
Range
00:00 – 23:50; nu
SUN (0-SUN)
MON (1-MON)
TUE (2-TUE)
WED (3-WED)
THU (4-THU)
FRI (5-FRI)
SAT (6-SAT)
nu (7-NU)
cn (0-CN)
on (1-ON)
cy (2-CY)
oy (3-OY);
-40°C to 110°C
0 to 59°C
0 to 255 min
0 to 255 min
NU (0-NU)
Mid-coil temperature (1-MCT)
Discharge line temperature (2-DLT)
Ambient temperature (3-AMT)
Thermostat temperature (4-TMT)
G49 to 110°C
-40°C to G48
0.1°C to 25.5°C
0 to 255 sec
0 to 255 min
0 to 255 min
0 to 255 min
0 to 255 min
no; yes
no; yes
no; yes
Factory setting
ZXDE ZXME ZXLE
L2
L2
20:00
SUN
L2
L2
L2
L2
SUN
cn
L2
L2
0
L2
L2
2
L2
L2
L2
L2
1
1
L2
L2
Not used
L2
L2
10
L2
L2
-25
L2
L2
L2
L2
3
60
L2
L2
20
L2
L2
3
L2
L2
1
L2
L2
1
L2
L2
L2
L2
NO
YES
L2
L2
YES
L2
L2
L2
L2
L2
L2
L2
L2
L2
L2
L2
L2
L2
L2
L2
L2
L2
L2
L2
L2
L2
L2
57