6. Click OK in the Add dialog box. The point will be added to the Database and the Points folder.
7. In the Nav tree, browse to the WEB-RS5N slave controller.
8. Expand the IRM Program folder.
9. In the control manager of the WEB-RS5N slave controller, set the drop option for BACnet output dropping
(mandatory for outputs and value points, but not necessary for input points, see previous subsection).
Based on the example, select ´Create RefInput' in Drop of Bacnet Output.
10. Double-click the control program folder, Periodic Program or Event Program, to which you want to add the
´FanStage` BACnet point.
SPYDER MODEL 5 ENGINEERING TOOL – USER GUIDE
79
31-00282ES-01