8. Click Save.
NOTE: If any of the configuration settings are changed during operation, you must restart the CIPer Model 50
controller (see also Baud rate Note).
9. Commission the CIPer Model 50 station to the CIPer Model 50 controller (standard Niagara procedure).
NOTE: For detailed information on standard Niagara techniques and functions, please refer to the Niagara online
documentation and/or the CIPer Model 50 Controller User Guide: 31-00198-01.
Baud rate Note
The following baud rates for the MSTP interface in the Spyder Model 5 controller are supported:
9600
19200
38400 (default)
57600
76800
The baud rate of each Spyder Model 5 controller on the BACnet MSTP bus is automatically set by the defined baud rate
of the BACnet IP - MSTP Router (CIPer Model 5) controller after the Spyder Model 5 controller is powered up and
connected to the BACnet MSTP bus.
Setting/changing the baud rate of a single Spyder Model 5 controller is not possible.
When changing the baud rate of the BACnet MSTP bus of a running system, any connected Spyder Model 5 controller
must be power-cycled to adapt the changed baud rate.