The Control Manager Procedure - Honeywell Spyder 5 User Manual

Engineering tool
Hide thumbs Also See for Spyder 5:
Table of Contents

Advertisement

SPYDER MODEL 5 ENGINEERING TOOL – USER GUIDE

The Control Manager Procedure

1.
In the Nav tree, expand the IRM Program folder.
2. Double-click on Control Manager icon.
RESULT: On the Property Sheet, the following information is displayed.
Author of the application.
Description.
Application Type.
Function Block Family.
Function Block Version.
Number of Folders.
Numver of function blocks.
Number of Links.
Memory usage shows the memory usage of the device, application and parameters in percentage and graphically.
Controller Hardware features displays the I/O configuration (Online available in Online mode).
Hardware compatibility indicates weather the terminal layout of the application is compatible with the hardware
layout of the physical controller.
Controller connection allows selecting the connection type from: network, offline, and simulation.
Teaching mode allows selecting the teaching mode from on demand and immediate .
Measurement Type allows selecting the type of engineering units from SI-metric or Imperial.
Drop of BACnet Output defines which type of reference point, reference input or output is created when dropping a
BACnet output from another device.
Drop of BACnet Value defines which type of reference point, reference input or output is created when dropping a
BACnet value point from another device.
Communication Status displays the communication status of the device: online or offline.
Is Synchronized indicates whether the project and the controller are synchronized (yes) or not (no).
Synchronization status displays a message describing the cause of the current synchronization status.
Last program change displays the date of the last program change.
Last Commissioned displays the date of the last commissioning.
3.
Do any of the following if desired:
a.
In Controller Connection, select the connection type for the devices from:
Network connects to the physical BACnet network.
-
Offline disables the connection to the network. This is useful in case you want to reduce bus traffic if the
-
application has not been swapped out.