Honeywell Spyder 5 User Manual page 51

Engineering tool
Hide thumbs Also See for Spyder 5:
Table of Contents

Advertisement

b.
In Teaching Mode, select how the application changes in the project are written to the controller from:
Immediate changes are written to the controller automatically and are effective immediately.
-
on demand changes are written to the controller manually and explicitly by the Teach to Controller action.
-
NOTE: For both teaching modes, only the changes are written to the device, hence the process is very fast.
c.
In Measurement Type, select the type of engineering units from:
SI-metric
-
Imperial
-
4.
Click Save.
Memory Usage
The memory of the controller´s RAM is max. 344 KB and is consumed by the:
Device
Application
parameters
The Spyder Model 5 Engineering Tool provides a memory consumption check of the current application in the tool. This
is an approximate calculation of the application in the tool but not a real-time consumption within the controller.
The calculated memory usage is shown in the IRM Manager as percentage and graphically via traffic light symbol.
Memory Usage and Its Display
The max. number of memory in the controller is 344 KB.
Each folder added consumes 8 KB of memory. The max. number of folders is 36, 4 folders are reserved by default. Hence,
user-defined individual folders can be 32 at max.
The calculated memory consumption will be indicated graphically and as percentage in the traffic light symbol as
follows:
Green < 80 %
Yellow >80 %
Red >90 %
The memory usage can be viewed on the property sheets of the following different levels:
IRM Program (percentage)
Control Manager (percentage and graphically)
Periodic and Event Program and its subfolders (percentage)
SPYDER MODEL 5 ENGINEERING TOOL – USER GUIDE
51
31-00282ES-01