Superheat controller – oem version

Advertisement

Available languages

Available languages

Quick Links

GENERAL
The OEM SHC Controller comes complete with base plate,
main board, plug-in board, and a set of terminal blocks.
Fig. 1. OEM SHC Controller
There are two configurations to choose from, depending
upon your desired application:
Configuration for Brine-to-Water Heat Pumps: Control
algorithm for liquid/liquid refrigeration circuit is pre-
selected. Use of Honeywell temperature sensor type TS-
NFR and Honeywell pressure sensor type PSR is
required. Application-specific settings available, upon
request.
Configuration for Air-to-Water Heat Pumps: Control
algorithm for air/liquid refrigeration circuit is pre-selected.
Use of Honeywell temperature sensor type TS-NFR and
Honeywell pressure sensor type PSR is required.
Application-specific settings available, upon request.
BEFORE INSTALLATION
IMPORTANT
It is recommended that the SHC Controller be kept at
room temperature for at least 24 hours before apply-
ing power; this is to allow the evaporation of any
condensation resulting from low shipping / storage
temperatures.
® U.S. Registered Trademark ▪ All Rights Reserved.
Copyright © 2010 Honeywell Inc.
SUPERHEAT CONTROLLER – OEM VERSION
CAUTION
The product may be mounted only by trained personnel who are
thoroughly familiar with all pertinent electrical safety rules.
To avoid electrical shock or equipment damage, you must turn
OFF the power supply before attaching / removing connections
to/from any terminals.
Do not power the SHC with line voltage!
If the product is mounted where unauthorized personnel has
access, the relays may not be used for switching line voltage
(230 Vac).
In case of relays switching line voltage, two neighboring relays
may switch the same phase, only.
Sensors and secondary (output) of transformer may not be
grounded simultaneously.
Grounding of secondary (output) of transformer is not
recommended.
Alarm relay without power must be recognized as "alarm" if used.
A 24 V emergency battery module (not included) can be
connected to the SHC to enable safe closing in the event of a
power failure. 1 Ah is recommended.
Sensors with current output 4...20 mA and ratiometric voltage
output 0.5 V...4.5 V may not be used simultaneously.
Connecting sensors by wires more than 6 m long may decrease
the accuracy of measured values.
To prevent damage to the compressor, the signal indicating
whether the compressor is running or not must be connected to
the SHC's enabler input in case the SHC is in the Automatic
Superheat Control mode while COLD STORE supervision is
disabled. If the SHC is operating in the Automatic Superheat
Control mode and COLD STORE supervision is simultaneously
enabled, the enabler input can be used (e.g., for main power
indication), but it may not be connected with compressor. If the
SHC is operating in any mode other than the Automatic
Superheat Control mode, the enabler input is ignored.
If supply voltage has been accidentally applied to the
voltage/current input, wait at least 15 minutes before switching
the SHC ON.
Disabling the Low superheat alarm and High superheat alarm is
not recommended.
Possible LOP alarm will be erased automatically when the SHC
enters the MANUAL, REMOTE, or CONFIGURATION mode.
A switch or circuit-breaker must be included in the installation; it
must be installed in close proximity to the controller and must be
marked as the disconnecting device for the controller.
If one of the supported Honeywell transformers (see section
"Accessories") is not used to supply the SHC controller, protect
the power input line G using an external 3A type T fuse.
Type SHC
INSTALLATION INSTRUCTIONS
MU1B-0441GE51 R0710B

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell SHC Series

  • Page 1 Application-specific settings available, upon request. marked as the disconnecting device for the controller. • If one of the supported Honeywell transformers (see section “Accessories”) is not used to supply the SHC controller, protect BEFORE INSTALLATION the power input line G using an external 3A type T fuse.
  • Page 2 OEM SHC CONTROLLER – INSTALLATION INSTRUCTIONS Approvals, Certifications, and Standards Approvals and Certifications • CE-approved according to IEC60730 • No hazardous substances according RoHS 2002/95/EC • Waste disposal according Waste Electrical and Electronic Equipment Guideline WEEE 2002/96/EEC Classification according to EN60730-1 Environmental conditions: For use in home (residential, commercial, and light-industrial)
  • Page 3: Terminal Assignment

    OEM SHC CONTROLLER – INSTALLATION INSTRUCTIONS Terminal Assignment 154 mm The terminal blocks are arranged on two sides of the con- troller: the sensor side and the relay side. The terminals on round hole the controller consist of multiple sockets for screw terminal (diameter: 4 mm) plugs which come together with the controller.
  • Page 4 OEM SHC CONTROLLER – INSTALLATION INSTRUCTIONS Table 1. Terminal assignment term. # name description voltage supply 24 Vac/dc (+) voltage supply 24 Vac/dc (-) buffer battery module 24 V (+) with power level indicator EARTH earth / shielding OUT2B output 2B of stepped motor OUT2A output 2A of stepped motor OUT1B output 1B of stepped motor OUT1A output 1A of stepped motor...
  • Page 5: General Information

    OEM SHC CONTROLLER – INSTALLATION INSTRUCTIONS Table 2. LED blinking patterns and corresponding meanings behavior meaning LED 1 Power is ON. (green power LED) always ON always OFF No alarm single blink Power failure (the SHC will then run on battery) 2 blinks Low superheat alarm is active 3 blinks...
  • Page 6: Hardware Features

    1…1,000 steps after unplugging them from a unit requiring repair or replacement. Besides the Honeywell electronic expansion valve type EEV (models EV2, EV3, EV4), the controller provides presettings Wiring the Inputs/Outputs for the stepper motor valves listed in Table 3 with the cor- responding parameters.
  • Page 7: Relay Outputs

    OEM SHC CONTROLLER – INSTALLATION INSTRUCTIONS Relay Outputs NOTES:  If the product is mounted on the wall or in an installation The controller provides in total 4 relay outputs: cabinet to which unauthorized personnel has access, the  1 change-over (SPDT) relay, connected to terminals 12 to relays must not be used for switching line voltage 14 and (230 Vac).
  • Page 8: Analog Output

    (0.5…4.5 V / 0...10 V) or current (4…20 mA) input. NOTE: For description of SAFE procedure and START up procedure refer to Operating Instructions which can be downloaded from webpage www.honeywell- Accuracy (without sensor) cooling.com The accuracy of AIN5 and AIN6 configured for voltage input is max.
  • Page 9: Direct Mode

    OEM SHC CONTROLLER – INSTALLATION INSTRUCTIONS REVERSE OPERATION Digital Input  If sensor setting is made wrong, the controller will signal configuration error. If the REVERSE OPERATION digital input (terminals 35/36) is active, the appliance controller signals that the circuit is in the REVERSE mode.
  • Page 10: Sample Applications

    SHC-X9999 SHC OEM with customized configuration Contact Honeywell Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative: Automation and Control Solutions Honeywell GmbH...
  • Page 11: Vor Inbetriebnahme

    Der SHC Überhitzungsregler muß für mindestens 24 sein muß. Stunden bei Raumtemperatur gelagert werden, bevor • Falls keiner der unter Zubehör genannten Honeywell Transfor- er an die Spannungsversorgung angeschlossen wird. matoren benutzt wird (siehe „Zubehör“), muß der SHC Regler am Hierdurch kann das durch Transport bei tieferen Tem- Spannungseingang G mit einer externen 3A Träge abgesichert...
  • Page 12: Installation

    ÜBERHITZUNGSREGLER OEM VERSION – MONTAGEANLEITUNG Zulassungen, Zertifikate und Standards Montage/Demontage auf DIN Schiene Zulassungen und Zertifikate Der Regler kann durch einfaches Aufschnappen auf eine DIN Schiene montiert werden und mit einem Stopper gegen • CE-Kennzeichnung gemäß IEC60730 Verrutschen gesichert werden. Er wird demontiert durch •...
  • Page 13 ÜBERHITZUNGSREGLER OEM VERSION – MONTAGEANLEITUNG  Die Sensorseite (Klemmen 21-39) besteht aus Klemmen HINWEIS: Gemäß VDE Richtlinie ist eine Mischung von für sechs Analogeingänge, einen Analogausgang und Hoch- und Niederspannungssignalen an den drei Digitaleingänge. Relais nicht erlaubt.  Die Relaisseite (Klemmen 1-20) besteht aus Klemmen für die Spannungsversorgung (24 Vac/dc), den Steppermotor Ausgang, die RS485 Schnittstelle und die vier Relais.
  • Page 14 ÜBERHITZUNGSREGLER OEM VERSION – MONTAGEANLEITUNG Tabelle 1. Klemmenbelegung Kl.-Nr. Name Beschreibung Spannungsversorgung 24 Vac/dc (+) Spannungsversorgung 24 Vac/dc (-) Pufferbatterie-Modul 24 V (+) mit Ladekontrolle EARTH Masse / Abschirmung OUT2B Ausgang Schrittmotor 2B OUT2A Ausgang Schrittmotor 2A OUT1B Ausgang Schrittmotor 1B OUT1A Ausgang Schrittmotor 1A RS485, Leitung A + RS485, Leitung B -...
  • Page 15 ÜBERHITZUNGSREGLER OEM VERSION – MONTAGEANLEITUNG Tabelle 2. LED Blink-Kodierung Verhalten Bedeutung LED 1 (grüne Spannungsvers.- Versorgungsspannung liegt an. LED) Kein Alarm Batterieversorgung Zu niedrige Überhitzung LED 2 Zu hohe Überhitzung (rote Alarm-LED) Sensor Fehler LOP aktiv Konfigurationsfehler Kommunikationsfehler Fehler in Hardware Selbsttest Anlage ist ausgeschaltet (Sicherheitsposition) Einschaltphase oder EEV aktiv (öffnet/schließt) Umschaltrelais aktiv, Umschaltverzögerung läuft...
  • Page 16 HARDWARE FUNKTIONEN Neben den elektronischen Expansionsventilen Typ EEV von Schrittmotor-Ausgang Honeywell (Modelle EV2, EV3, EV4) hat der Regler Vor- einstellungen für die in Tabelle 3 gelisteten Schrittmotor- ventile mit den zugehörigen Parametern. Diese Ventile Der Regler kann bipolare Schrittmotoren mit 12 V oder mit 24 können einfach durch Anwahl des Ventiltyps konfiguriert...
  • Page 17 ÜBERHITZUNGSREGLER OEM VERSION – MONTAGEANLEITUNG  Falls die Relais Netzspannung schalten, dürfen zwei HINWEISE: benachbarte Relais nur dieselbe Phase schalten.  Bei Wandmontage und bei Montage im Schaltschrank, zu  Das Wechsel-Relais wird immer als Alarm Relais dem ungeschultes Personal Zugang hat, dürfen die verwendet.
  • Page 18 HINWEIS: Die SAFE-Prozedur und die START-Prozedur sind Spannungseingang, ist max. ±1%. in im Betriebshandbuch beschrieben, das von der Die Genauigkeit von AIN5 und AIN6, konfiguriert als Internetseite www.honeywell-cooling.com Stromeingang, ist max. ±2.5%. heruntergeladen werden kann Eingangswiderstand CLOSE-Digitaleingang Der Eingangswiderstand von AIN5 und AIN6, konfiguriert als Wenn der CLOSE-Digitaleingang (Klemmen 37/38) von Spannungseingang, ist min.
  • Page 19 ÜBERHITZUNGSREGLER OEM VERSION – MONTAGEANLEITUNG  Wenn Sensor Einstellungen falsch gewählt werden, Tabelle 6. Digitaleingang Parameter signalisiert der Regler Konfigurationsfehler. Parameter Grenzen / Beschreibungen ENABLER- CLOSED: Aktiv bei Kontakt GESCHLOSSEN Digitaleingang OPEN: Aktiv bei Kontakt OFFEN EVAP. FLUID SUPPLY UNDEFINED: Eingang nicht verwendet REVERSE TEMP.
  • Page 20 SHC-X9999 SHC OEM mit kundenspezifischer Konfiguration Kontaktieren Sie Honeywell Hergestellt für und im Auftrag des Geschäftsbereichs Environmental and Combustion Controls der Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Schweiz in Vertretung durch: Automation and Control Solutions Honeywell GmbH Hardhofweg...

Table of Contents