SPYDER MODEL 5 ENGINEERING TOOL – USER GUIDE
16. Click Save.
17. The reference input in the WEB-RL6N master controller is mapped to the multistate value point ´EffWindow` in the
WEB-RS5N controller which provides the window contact status.
18. Apply the procedure in the same way for:
Reading the room temperature by mapping a reference input from the master controller to the analog value
[ExtWmRmTemp] of the external BACnet Wall Module
Reading the fan stage by mapping a reference input from the WEB-RS5N slave controller to the multistate output
[FanStage] of the WEB-RL6N master controller.