5.1.3
Electrostatic charge
When liquid measured by NMS8x has a conductivity of 1 uS/m or less, it is quasi-
nonconductive. In this case, using a stilling well or guide wire is recommended. This releases
the electrostatic charge on the liquid surface.
5.2
Mounting of the device
The NMS8x is delivered in two different packing styles depending on the mounting method of
the displacer.
• For the all-in-one method, the displacer is mounted on the measuring wire of NMS8x.
• For the displacer shipped separately method, it is necessary to install the displacer on the
measuring wire inside NMS8x.
5.2.1
Available installations
The following installation procedures are available for NMS8x.
• Mounting without guide system
• Mounting with stilling well
• Mounting with guide wire
Mounting
options
(Free-space mounting)
Type of tanks
Type of
• All-in one
installations
• Displacer shipped separately
• Displacer installation through
calibration window
Endress+Hauser
Without guide system
With stilling well
• All-in one
• Displacer shipped separately
• Displacer installation through
calibration window
Installation
With guide wire
Displacer shipped separately