13.2

Interface errors

Error
No communication via
CANopen interface
CAN continuous red
light LED
Sporadic errors at the
CANopen interface
Figure 13.1: Interface error
Notice!
Please use chapter 13 as a master copy should servicing be required.
Cross the items in the "Measures" column which you have already examined, fill out the
following address field and fax the pages together with your service contract to the fax
number listed below.
Customer data (please complete)
Device type:
Company:
Contact partner / department:
Phone (direct):
Fax:
Street / No:
ZIP code/City:
Country:
Leuze Service fax number:
+49 7021 573 - 199
Leuze electronic
Possible error causes
Incorrect wiring.
Incorrect baud rate / address
different baud rate setting in con-
trol and MA: no communication.
Address >99: no communication.
Incorrect wiring.
Effects due to EMC.
Overall network expansion
exceeded.
MA
235i
Diagnostics and troubleshooting
Measures
Check wiring.
Check switch settings:
Baud rate selector switch S3.
Address switch S1, S2.
Check wiring.
In particular, check wire shielding.
Check the cable used.
Check shielding (shield covering in place up to
the clamping point).
Check grounding concept and connection to
functional earth (FE).
Avoid EMC coupling caused by power cables laid
parallel to device lines.
Check max. network expansion as a function of
the max. cable lengths.