Setting the read parameters on the Leuze device

Commissioning the Leuze device
To commission a read station, you must prepare the Leuze device on the MA
reading task. Communication with the Leuze device occurs via the service interface.
Notice!
For further information on connecting and using the service interface, see chapter 9 "Con-
figuration".
 To do this, connect the Leuze device to the MA 235i.
Depending on the Leuze device, this occurs either via a connection cable (accessory no.:
KB 031-1000) or directly on the MA 235i. The service connector and corresponding
switches can be accessed with the housing cover open.
 Select the "DEV" service switch position.
Connect the service interface; call up the terminal program
 Connect your PC to the service connector via the RS 232 cable.
 On the PC, call up a terminal program (e.g., BCL-Config) and check whether the interface
(COM 1 or COM 2) to which you have connected the MA
standard setting: 9600 baud, 8 data bits, no parity, 1 stop bit and STX, data, CR, LF.