Customer service

6.5.1
Replacing the set point
springs
Type 2371-11 · Set point springs
You need to replace the set point springs (7)
with both plates to achieve a different set
point range. We recommend changing the
entire actuator housing (8) with set point
springs (7) and set point screw (6).
How to proceed:
The regulator does not need to be removed
from the pipeline.
See section 6.4 on page 21, steps 2 and
3.
Type 2371-11 ∙ Actuator housing with internal set
point springs
Fig. 14: Exchanging the set point springs
24
7 Customer service
If malfunctions or defects occur, contact the
SAMSON After-sales Service Department for
support.
Please e-mail inquires to:
aftersalesservice@samson.de
The addresses of SAMSON AG, its subsid-
iaries, representatives and service facilities
worldwide can be found on the SAMSON
website (u www.samson.de), in all
SAMSON product catalogs or on the back
of these Mounting and Operating Instruc-
tions.
To assist diagnosis and in case of an unclear
mounting situation, specify the following de-
tails (see section 8 on page 25):
− Type designation and modification index
− Nominal size DN
7
− Serial number
− Temperature and process medium
8
− Is a strainer installed?
− Installation drawing showing the exact
location of the regulator and all the ad-
ditionally installed components (shut-off
valves, pressure gauge, etc.)