Figure 4-4:
Note
The set permanent address and tag process takes about 1 to 2 minutes to
complete.
6. Repeat steps 2 through 5 for each device on which you want to set a
permanent address.
4.5
Set Fieldbus Device Default Address
Device address can be set to a default address, which decommissions the
device.
Note
Fieldbus devices on a live segment cannot be decommissioned.
1. Launch the USB Fieldbus Interface Configuration utility.
2. Double-click the Fieldbus device icon you want to configure. A device
screen is displayed.
Note
A connected fieldbus device or segment should be powered by an
external power source or by the USB Fieldbus Interface Configuration
utility for it to be detected.
Set Permanent Address and Tag
User's Manual
21