Nominal frequency
Frequency range
Bypass voltage range
Noise filtering
Model
6K 16PCS BAT
6KS 16PCS BAT
10K 16PCS BAT
10KS 16PCS BAT
Table 5. Electrical input connections
Model
6K/6KS
10K/10KS
Table 6. Electrical output
All models
Voltage regulation
Efficiency
Frequency regulation
Nominal output
Frequency
Output overload
Output overload
(Bypass mode)
Voltage waveform
50/60Hz auto-sensing
40 Hz– 70 Hz ≤60% rated load
45 Hz– 55 Hz(50Hz system)
54 Hz – 66 Hz (60Hz system) >60% rated load
45 Hz– 55 Hz
54 Hz – 66 Hz
>60% rated load
176~264Vac (default)
MOV for normal and common mode noise
Default input
(Voltage/Current)
230V / 31.2A
230V / 38.7A
230V / 49.9A
230V / 57.6A
Input connection
Hardwired
Normal mode
±1%
> 98% (High Efficiency mode)
> 95%
Sync with line ±10% of nominal line
frequency (outside this range: ±0.1%
of auto-selected nominal frequency)
208V*, 220V, 230V, 240V (voltage configurable)
6000/10000VA* 6000/10000W*
50 or 60Hz, autosensing or configurable as a frequency
converter
100-105% : no alarm
105-125% : load transfers to Bypass mode after 10 minutes
125-150% : load transfers to Bypass mode after 30s
> 150% : load transfers to Bypass mode after
100-105% : no alarm
105-125% : continue working and alarm
125-150% : UPS shuts down after 30s
Sinewave
31
Voltage
at 100% Load
176~275Vac
176~275Vac
176~275Vac
176~275Vac
Input cable
Not provided
Battery mode
±1%
> 93%
±0.1% of auto-selected
nominal frequency