Santak CASTLE RACK 6K User Manual page 39

Table of Contents

Advertisement

Nominal frequency
Frequency range
Bypass voltage range
Noise filtering
Model
6K 16PCS BAT
6KS 16PCS BAT
10K 16PCS BAT
10KS 16PCS BAT
Table 5. Electrical input connections
Model
6K/6KS
10K/10KS
Table 6. Electrical output
All models
Voltage regulation
Efficiency
Frequency regulation
Nominal output
Frequency
Output overload
Output overload
(Bypass mode)
Voltage waveform
50/60Hz auto-sensing
40 Hz– 70 Hz ≤60% rated load
45 Hz– 55 Hz(50Hz system)
54 Hz – 66 Hz (60Hz system) >60% rated load
45 Hz– 55 Hz
54 Hz – 66 Hz
>60% rated load
176~264Vac (default)
MOV for normal and common mode noise
Default input
(Voltage/Current)
230V / 31.2A
230V / 38.7A
230V / 49.9A
230V / 57.6A
Input connection
Hardwired
Normal mode
±1%
> 98% (High Efficiency mode)
> 95%
Sync with line ±10% of nominal line
frequency (outside this range: ±0.1%
of auto-selected nominal frequency)
208V*, 220V, 230V, 240V (voltage configurable)
6000/10000VA* 6000/10000W*
50 or 60Hz, autosensing or configurable as a frequency
converter
100-105% : no alarm
105-125% : load transfers to Bypass mode after 10 minutes
125-150% : load transfers to Bypass mode after 30s
> 150% : load transfers to Bypass mode after
100-105% : no alarm
105-125% : continue working and alarm
125-150% : UPS shuts down after 30s
Sinewave
31
Voltage
at 100% Load
176~275Vac
176~275Vac
176~275Vac
176~275Vac
Input cable
Not provided
Battery mode
±1%
> 93%
±0.1% of auto-selected
nominal frequency