When choosing a base, mid-level, or premium Power Conditioning system, an
upgrade to the next level may be required if problems arise. This could be due to
power problems generated by the power company or other equipment in the
building.
AC Power Consumption and Volt-Amp Ratings for MICROS
Equipment
The following information is provided to assist in calculating the UPS and power
conditioner size requirements. The ratings for MICROS workstations and peripheral
equipment are close to actual. When using the actual ratings, add 20% to the total to
account for variations in your systems power consumption.
The Ampere and Volt-Ampere ratings listed below assume a 120Volt AC ~10%, single
phase, 60 Hz ~3% input.
Table 22-2
Device
MICROS Workstations
Workstation 6
Workstation 5A
Workstation 5A w/
Protégé
Workstation 5
Workstation 4/4 LX
Keyboard Workstation
4
Keyboard Workstation
270 /w No Battery
Keyboard Workstation
270 /w Battery
Charging.
Keyboard Workstation
270 /w Battery Fully
Charged.
PC Workstation 2010
PC Workstation
2010 /w TM-T88
PC Workstation 2015
PC Workstation 2015
with Protégé
MICROS Tablet Base
Station
with optional Battery,
Printer, Scanner
AC Power Consumption and Volt-Amp Ratings for MICROS Equipment
AC Power Consumption of MICROS Hardware Devices
Amp (A)
0.14
0.36
0.44
0.30
0.22
0.22
0.11
0.50
0.11
0.47
0.53
0.55
0.61
0.31
VA (VA)
Backlight ON
(W)/(A)/(VA)
16
9/0.14/16
44
26/0.36/44
52
31/0.44/52
35
23/0.30/35
26
22/0.22/26
26
N/A
13
N/A
61
N/A
13
N/A
55
38/0.39/48
94
N/A
67
45/0.55/67
77
49/0.61/77
36
N/A
Chapter 22
Backlight Off
(W)/(A)/(VA)
7/0.12/14
15/0.21/25
N/A
13/0.20/25
15/0.15/18
N/A
N/A
N/A
N/A
28/0.3/34
N/A
18/0.25/30
N/A
N/A
22-6
Need help?
Do you have a question about the MICROS 700 Series and is the answer not in the manual?