•
Wireless Access Points
Install Wireless Access Point(s) after a site survey is performed by a qualified
wireless professional.
Connect Wireless Access Point(s) to a dedicated, isolated ground AC outlet
installed in accordance with the procedures outlined in the
Requirements
section.
•
MICROS Workstations
Each MICROS Workstation location requires a Category 6 faceplate and patch
cable. Each MICROS workstation requires a dedicated, isolated ground AC outlet
installed in accordance with the procedures outlined in the
Requirements
section.
•
IP Printers
The IP Printer is any supported Epson model equipped with Ethernet Module.
Each printer requires one Ethernet channel as well as a dedicated, isolated ground
AC outlet installed in accordance with the procedures outlined in the
Requirements
section.
•
Order Confirmation Controller
The Order Confirmation Controller requires a Category 6 faceplate and patch
cable to connect to the POS application. It also requires a second Category 5e or
better faceplate and patch cable as well as a Category 5e or better cable run to
the Remote Display Unit housed in the pedestal.
The
Installing the Order Confirmation System
instructions for the Order Confirmation System.
•
Digital Menu and Marketing Board Controller
Each Digital Menu Board Controller in a system requires a Category 6 or better
Ethernet faceplate and patch cable. Each Digital Menu Board Controller(s) and
each LCD monitor requires a dedicated, isolated ground AC outlet installed in
accordance with the procedures outlined in
•
e7 KVM Controller
If the KVM Controller Ethernet port is used, place the Category 6 or better Face
Plate and Patch Cable near the unit and host workstation. The
Requirements
section contains more information.
The KVM Controller, Monitors, and optional printer require the Preferred AC Power
System detailed in the
•
IP Printers
The IP Printer is any supported Epson model equipped with Ethernet Module.
Each printer requires one Ethernet channel as well as a dedicated, isolated ground
AC outlet installed in accordance with the procedures outlined in the
Requirements
section.
•
Order Confirmation Controller
The Order Confirmation Controller requires a Category 6 faceplate and patch
cable to connect to the POS application. It also requires a second Category 5e or
better faceplate and patch cable as well as a Category 5e or better cable run to
the Remote Display Unit housed in the pedestal.
The
Installing the Order Confirmation System
instructions for the Order Confirmation System.
section provides installation
theAC Power Requirements
AC Power Requirements
section provides installation
Structured Cabling Examples
AC Power
AC Power
AC Power
section.
Cable
section.
AC Power
Chapter 26
26-5
Need help?
Do you have a question about the MICROS 700 Series and is the answer not in the manual?