5.1.2

From the function table to the logic diagram

Creating a logic diagram
In the next step, a simple logic diagram is made from the function table. The fail-safe inputs
of the TM54F must be connected and this diagram serves as the basis for this.
The logic diagram has a few functions that are not listed in the function table:
● Emergency stop is executed with SS1.
● In order to acknowledge SI alarms, a safe input as acknowledgment is necessary.
● Only SLS2 and SLS4 are used for SLS.
SLS1 active
SLS2 active
SLS3 active
SLS4 active
SLS selection bit 0 is set permanently to "1" when configuring the TM54F, i.e. "Statically
inactive" in STARTER. The inputs for the TM54F can be assigned as follows:
Input
F-DI 0
F-DI 1
F-DI 2
F-DI 3
Safety Integrated
Function Manual, 07/2012, 6FC5397-3EP40-3BA0
SLS selection bit 1
0
0
1
1
Function
Emergency stop, deselection of
SS1
Deselection of SOS
(Safe Operating Stop)
Activation of SLS bit 1
(SLS bit 0 is permanently 1)
Safe acknowledgement - for the
acknowledgement of safety
alarms, if acknowledgeable.
This F-DI may not have level "1"
continuously.
Example of commissioning with SINUMERIK 828D
SLS selection bit 0
0
1
0
1
The function is specified in STARTER:
<Project name>\Drive unit\Input/output
components\TM54F\Safety Integrated\
Drive group 1 to 4
<Project name>\Drive unit\Input/output
components\TM54F\Safety Integrated\
Configuration
5.1 Planning
37