132 Technical data
Tightening torques
Unless a tightening torque is specified in the text, the following torques can be used.
■
Electrical connections
Size
M3
0.5 N·m (4.4 lbf·in)
M4
M5
M6
M8
M10
M12
M16
120 N·m (90 lbf·ft)
■
Mechanical connections
Size
M5
M6
10 N·m (7.4 lbf·ft)
M8
24 N·m (17.7 lbf·ft)
■
Insulation supports
Size
M6
M8
M10
18 N·m (13.3 lbf·ft)
M12
■
Cable lugs
Size
M8
M10
32 N·m (23.5 lbf·ft)
M12
Input power (DC bus) connection
Voltage (U
)
1
Drive AC supply network
type
Input terminals
Torque
1 N·m (9 lbf·in)
4 N·m (35 lbf·in)
9 N·m (6.6 lbf·ft)
22 N·m (16 lbf·ft)
42 N·m (31 lbf·ft)
70 N·m (52 lbf·ft)
Max. torque
6 N·m (53 lbf·in)
Max. torque
5 N·m (44 lbf·in)
9 N·m (6.6 lbf·ft)
31 N·m (23 lbf·ft)
Max. torque
15 N·m (11 lbf·ft)
50 N·m (37 lbf·ft)
ACS880-1604LC-xxxxx-7 = 742 ... 976 V DC. This is indicated in the type designa-
tion label as typical input voltage levels 742 / 849 / 976 V DC (849 V DC for
UL/CSA).
TN (grounded) and IT (ungrounded) systems, corner-grounded systems up to
600 V AC.
See the dimension drawings.
Note
Strength class 4.6...8.8
Strength class 4.6...8.8
Strength class 8.8
Strength class 8.8
Strength class 8.8
Strength class 8.8
Strength class 8.8
Strength class 8.8
Note
Strength class 8.8
Strength class 8.8
Strength class 8.8
Note
Strength class 8.8
Strength class 8.8
Strength class 8.8
Strength class 8.8
Note
Strength class 8.8
Strength class 8.8
Strength class 8.8