Download Print this page

Fuses - ABB ACS880-1604LC Hardware Manual

Dc/dc converter modules
Hide thumbs Also See for ACS880-1604LC:

Advertisement

128 Technical data

Fuses

The fuses are given in the ordering information.
Losses and cooling data
ACS880-
Frame
1604LC-...
U
= 690 V
N
0400A-7
R8i
0500A-7
R8i
0600A-7
R8i
0700A-7
R8i
0800A-7
R8i
0900A-7
R8i
1000A-7
2×R8i
1200A-7
2×R8i
1400A-7
2×R8i
1600A-7
2×R8i
1800A-7
2×R8i
ACS880-
module(s)
1604LC-...
U
= 690 V
N
0400A-7
0500A-7
0600A-7
0700A-7
0800A-7
0900A-7
1000A-7
1200A-7
1400A-7
1600A-7
1800A-7
P
(conv.)
loss
kW
3.3
4.1
4.7
5.5
6.4
7.2
8.9
10.6
12.7
14.8
17.1
Coolant volume
BDCL filter
l
1.9
2.6
1.9
2.6
1.9
2.6
1.9
2.6
1.9
2.6
1.9
2.6
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
P
(filter)
P
loss
loss
kW
0.9
1.2
1.5
1.8
2.1
2.5
2.3
3.0
3.6
4.2
4.9
module(s)
l
l/min
16
16
16
16
16
16
32
32
32
32
32
total
Pressure loss
kW
kPa
4.2
120
5.3
120
6.2
120
7.3
120
8.5
120
9.7
120
11.2
120
13.6
120
16.3
120
19.0
120
22.0
120
Coolant flow rate
BDCL filter
l/min
20
20