Download Print this page

Protection Classes - ABB ACS880-1604LC Hardware Manual

Dc/dc converter modules
Hide thumbs Also See for ACS880-1604LC:

Advertisement

134 Technical data
Note:
The optical components (transmitter and receiver) on a fiber optic link must be of the same
type.
Plastic optical fiber (POF) cables can be used with both 5 MBd and 10 MBd optical
components. 10 MBd components also enable the use of Hard Clad Silica (HCS®) cables,
which allow longer connection distances thanks to their lower attenuation. HCS® cables
cannot be used with 5 MBd optical components.
The maximum lengths of fiber optic links for POF and HCS® cables are 20 and 200 meters
respectively.

Protection classes

Degrees of protection
(IEC/EN 60529)
Overvoltage category
(IEC/EN 60664-1)
Protective class
(IEC/EN 61800-5-1)
Efficiency
98.6...98.8% at nominal power level
Ambient conditions
The unit is to be used in a heated indoor controlled environment.
Altitude above sea level
Air temperature
Relative humidity
IP00
III
I
Operation installed for
stationary use
0...4000 m (13123 ft)*
Output derated above 1000
m (3281 ft). See section
Altitude derating.
*Neutral-grounded TN and
TT network systems, non-
corner-grounded IT net-
work systems. Corner-
grounded TN, TT and IT
network systems up to 600
V.
0 ... +45 °C
(+32 ... +113 °F), no con-
densation allowed. Output
derated in the range
+45 ... +55 °C
(+113 ... +131 °F).
Maximum 95%, no con-
densation allowed
No condensation allowed. Maximum allowed relative humidity is 60% in the presence
of corrosive gases.
Storage in protective
package
-
-40 ... +70 °C
(-40 ... +158 °F)
Maximum 95%, no con-
densation allowed
Transportation in protect-
ive package
-
-40 ... +70 °C
(-40 ... +158 °F)
Maximum 95%, no con-
densation allowed

Advertisement