110 Technical data
Losses, cooling data and noise
Converter type
ACS880-87LC-
U
= 690 V
N
4000A/4021A-7
4000A/4132A-7
Internal cooling circuit data
See chapter
Cooling and
Terminal and lead-through data for the grid connection
Each busbar consists of two parts placed against each other. You can connect cable lugs
to both sides of the connection busbar. Grid-side power connection enters the cabinet at
the bottom of the cabinet.
Tightening torques
Screw size
M5
M6
M8
M10
M12
M16
For the drawings and dimensions of the grid cable terminals, see chapter
drawings.
Losses
Liquid
Air
kW
kW
148
3
153
3
heating.
Torque
4 N·m (3 lbf·ft)
9 N·m (6.6 lbf·ft)
22 N·m (16.2 lbf·ft)
42 N·m (31 lbf·ft)
70 N·m (52 lbf·ft)
120 N·m (89 lbf·ft)
Cooling data
Coolant
Mass flow
quantity
(tolerance
-2%... +20%)
l
l/min
50
280
80
300
Noise
Pressure loss
kPa
dBA
100
< 70
100
< 70
3AXD10000011539
Dimension