Download Print this page

Ratings - ABB ACS880-1604LC Hardware Manual

Dc/dc converter modules
Hide thumbs Also See for ACS880-1604LC:

Advertisement

126 Technical data

Ratings

ACS880-
Frame
1604LC-...
U
= 690 V
N
0400A-7
R8i
0500A-7
R8i
0600A-7
R8i
0700A-7
R8i
0800A-7
R8i
0900A-7
R8i
1000A-7
2×R8i
1200A-7
2×R8i
1400A-7
2×R8i
1600A-7
2×R8i
1800A-7
2×R8i
Definitions
U
Nominal supply voltage of the drive
N
Nominal ratings
I
DC input current
DC
I
Continuous output current
rms
P
Maximum continuous active power
contmax
I
Maximum output current
max output
I
Peak-to-peak value of output current ripple measured after the filter
p2p
f
out
Switching frequency at output terminals (energy storage connection) measured after the filter
SW
I
I
P
DC
rms
contmax
input
output
A (DC)
A (DC)
kW
391
400
351
490
500
439
590
600
527
690
700
615
790
800
703
880
900
790
980
1000
878
1180
1200
1054
1370
1400
1230
1570
1600
1405
1760
1800
1581
No-overload use
P
I
contmax
max output
hp
A (DC)
471
500
589
625
707
750
824
875
942
1000
1060
1125
1178
1250
1413
1500
1649
1750
1884
2000
2120
2250
I
f
out
p2p
SW
A
Hz
38
12000
38
12000
56
12000
56
12000
56
12000
56
12000
19
24000
28
24000
28
24000
28
24000
28
24000

Advertisement

loading