94 Technical data
Tightening torques
■
Screw size
M5
M6
M8
M10
M12
M16
For the drawings and dimensions of the grid cable terminals, see the dimension drawings.
Terminal and lead-through data for the generator cables
You can connect cable lugs to both sides of the cable connection busbar. The lead-throughs
are acquired separately by the customer. Generator cables enter the cabinet in the plinth.
Generator cable connection busbars are presented below. See also the dimension drawings.
Torque
4 N·m (3 lbf·ft)
9 N·m (6.6 lbf·ft)
22 N·m (16.2 lbf·ft)
42 N·m (31 lbf·ft)
70 N·m (52 lbf·ft)
120 N·m (89 lbf·ft)