Parameter 744
Parameter 745
Parameter 746
Parameter 747
Store your data settings by means of Store Input (I4) or by changing Parameter 710 to "1".
68
Synchronizing controller
Step width: In marker synchronization mode, Offset Parameter 740 is changed
by this value when Terminal 32 or Terminal 33 is activated.
Slave speed factor: Record the factor by which the slave speed must be
multiplied, so that the desired value is displayed. To calculate the value use
the following formula:
N
*
400
*
Slaveencod
Set
Factor =
60
*
Example:
resolution 1024 increments, desired display 100 at 1500
1
1500
*
400 1024
min
Factor =
60 100
*
Master speed factor: Record the factor by which the master speed must be
multiplied, so that the desired value is displayed. To calculate the value use
the following formula:
N
*
400
*
Masterenco
Set
Factor =
60
*
Synchronizing error display factor: Record the factor by which the error must
be multiplied, so that the desired value is displayed. To calculate the value,
use the following formula:
N
*
400
*
Slaveencod
Set
Factor =
60
*
er
_
resolution
Display
_
value
Inkr
.
*
=
Umdr
.
102400
der
_
resolution
Display
_
value
er
_
resolution
Display
_
value
MG.10.N4.02 - VLT is a registered Danfoss trademark
1
/
min

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT 5000 and is the answer not in the manual?

Subscribe to Our Youtube Channel

This manual is also suitable for:

Vlt 5000 flux

Table of Contents