Danfoss VLT 5000 Operating Instructions Manual page 26

Synchronizing controller
Hide thumbs Also See for VLT 5000:
Table of Contents

Advertisement

Test run; Program 1:
727
Test run distance: Specify here the distance for the test run in quad counts.
Synchronous operation; Program 2:
Hold speed: If Hold function "0" was selected, enter here the speed as a percentage of
the maximum speed (Parameter 716).
Test run, program 1:
728
Synchronizing type (Sync type): This parameter is used to specify the type of synchroni-
zation used when optimizing the PID controller for synchronization by means of the virtual
master.
Setting range:
0
= Speed synchronizing
1
= Position synchronizing
Select "0" if you are going to use speed synchronizing in synchronous mode or select "1" if
you are going to use position or marker synchronizing in synchronous mode.
Synchronous operation; Program 2:
Delta hold speed: Specify the percentage by which the hold speed is to change when
Input 32 or 33 is activated during Hold mode.
MG.10.N4.02 - VLT is a registered Danfoss trademark
Synchronizing controller
25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt 5000 flux

Table of Contents