Figure 7 Piping Connections For Chilled Water Self-Contained Units - Emerson Liebert Challenger 3000 Installation Manual

Precision cooling for business-critical continuity, 3 & 5 tons, 50 & 60hz
Hide thumbs Also See for Liebert Challenger 3000:
Table of Contents

Advertisement

Figure 7
Piping connections for chilled water self-contained units
UPFLOW (BU) MODELS
Humidifier Water Supply
Line 1/4" OD CU
Condenser Re tu rn Line
7/8" OD CU on Models
BU046WG/BU045WG
1 1/8" OD CU on Models
BU071WG/BU070WG
Condensate Pump Line
1/2" OD CU
Used only if optional condensate
pump is ordered
Condensate Drain 3/4" FPT
Field pitch a min. of 1/8" (3.2mm) per ft. (305mm). Units without
a condensate pump have a factory-supplied trap in the unit, so a
field trap should not be added. Units with a condensate pump will
require a field-supplied trap downstream from the pump. The
drain line must comply with all applicable codes. (If condensate
pump is ordered piping is out top of unit).
Piping outlet locations through
the plenum are the same as the unit.
See below for descriptions and
connectoin sizes
Hot Water Return Line
5/8" OD CU (optional)
Condenser Supply Line
7/8" OD CU on Models
BU046WG/BU045WG
1 1/8" OD CU on Models
BU071WG/BU070WG
Hot Water Supply
5/8" OD CU (optional)
PIPING OUTLET LOCA TIONS
(See Cabinet and Floor Planning
Dimensional Data for Piping
10
Installation
Monitoring Panel
Opening Sizes.)
SL-11898 PG 9