Figure 31 2 And 3 Ton Water/Glycol Cooled Condensing Unit - Emerson Liebert Challenger 3000 Installation Manual

Precision cooling for business-critical continuity, 3 & 5 tons, 50 & 60hz
Hide thumbs Also See for Liebert Challenger 3000:
Table of Contents

Advertisement

Figure 31 2 and 3 ton water/glycol cooled condensing unit

3 7/8" (98mm)
8 7/16" (214mm)
Customer Supplied
Threaded Rods for Module
Support from Ceiling (typ. 4).
Holes for Module
Rigging (typ. 2 each end).
3/4" (19mm) N.P.T. Female
Water/Glycol Outlet Connecti o n.
Suction Line
Male Quick
Connect
Liquid Line
Male Quick
Connect
8 7/8" (225mm)
50 1/4" (1276mm)
Overall Dimension
48 1/4" (1225mm)
Threaded Rod Centers
46 1/2" (1181mm)
Cabinet Dimension
Outlet
Inlet
Integral Hanging Bracket
3/4" (19mm) N.P.T. Female
Water/Glycol Inlet Connecti o n.
7/8" (22mm) Dia.
Electrical Entrance
for Low Voltage Connection
14" (356mm)
Overall Cabinet
Dimension
12" (305mm)
Threaded Rod
Note:
Unit is Spaced Evenly in
Reference to Threaded Rod Centers.
DIMENSIONAL DATA
7/8" (22mm) Dia.
Electrical Entrance
for High Voltage
Connection.
PIPING CONNECTIONS
61
Split System Models
Centers
20 3/4"
(527mm)
22 1/2"
(572mm)
Cabinet
Dimension
Minimum Clearance
33" (838mm) This Side
for Component Access
and Removal.
SL-11085 PG 6

Advertisement

Table of Contents
loading