Chapter 2 Product Specification

2.2 Performance Specifications

The specifications for the Fnet I/F Module system configuration are as follows.
Please refer to Table 2.2.1 below for system configuration.
Classification
Max. Transmission
Distance
Max. No. Stations
Diagnostics Function
Terminating Resistance (Ω)
Master/Slave Function
XG-PD
(High Speed Link)
Station Numbering
Basic
Specifications
Note
1) XGR System is available for expansion base only, not for basic base.
2-2
[Table 2.2.1] Performance Specifications
Baudrate
Segment
Network
Cable
Network
Segment
Data Process Unit
Communication
Intervals
Max. Communication
Points
Max. No. of Blocks
Max. Point per Block 120 bytes (60 words)
Max. No. of
Transmission Blocks
No. of high speed link
usage
Max. No. of Modules 12 units (mountable on basic and expansion base)
Module Position
Internal Power
Consumption (mA)
Weight (g)
Specification
1Mbps
Max. 750m
Max. 750m + 6 repeaters (750m*6)= 5.25km
- Repeater expansion length: 750m
Twist pair shield cables.
- LIREV-AMESB 1Px22AWG (7/0.254): LS Cable
64 stations
32 stations
- Use repeaters for 32 or more stations
XG-PD: high speed monitoring
110(5%, 1/2W)
Available for master only
Byte
Select one of:20ms, 50ms, 100ms, 200ms, 500ms, 1s, 5s,
10s
- Default setting is 200ms
3780 words
64 (Transmission: 32, Reception: 64)
32 blocks
Max. 12
Set up in the basic setting window of XG-PD
XGK/XGI: mountable at any position.
XGR: available for expansion bases only.
410
115