Quick Start Guide
4
Align transmitter head
Procedure
1. Loosen the nut slightly and turn the transmitter.
2. Verify the transmitter head is properly aligned.
3. Tighten the nut.
16
60 mm
Option
Description
Open tank Align the marking on the sensor module toward the
tank wall (see
Still pipe
Align the external ground screw toward the holes of
the still pipe (see
Chamber
Align the external ground screw toward the process
connections (see
60 mm
Figure
4-1).
Figure
4-2).
Figure
Torque 355 in-lb (40 N-m)
Rosemount 5408 and 5408:SIS Level Transmitters
4-3).
June 2019