Configuring
6.2 Configuring the 3RW5 soft starter
1. Set the IP parameters in the 3RW5 communication module.
The following procedures are possible:
– Via SIRIUS Soft Starter ES (TIA Portal) over the local interface on the
– Via the 3RW5 HMI High Feature
Note
BOOTP/DHCP server
If the BOOTP/DHCP server is activated, you can only read the IP parameters. Deactivate
the BOOTP/DHCP server (Page 46) for the described procedures.
Observe the information in Chapter IP parameters (Page 45) and the alternative
procedure via a BOOTP/DHCP server (Page 46).
2. Integrate the 3RW5 soft starter in the configuration software of the controller with the EDS
file as an adapter in the EtherNet/IP system (Page 47).
3. Address the adapter (3RW5 soft starter) in the configuration software of the controller
with the aid of the previously set IP parameters.
Note the information in chapter IP parameters (Page 45).
4. Load the configuration into the scanner (if required).
Result
The 3RW5 soft starter is configured in the EtherNet/IP system, and can communicate with
other EtherNet/IP devices via the 3RW5 EtherNet/IP communication module.
44
3RW5 HMI High Feature
Menu: "Parameter > Communication module > Ethernet/IP > IP address"
Menu: "Parameter > Communication module > Ethernet/IP > Subnet mask"
Menu: "Parameter > Communication module > Ethernet/IP > Router address"
You will find more information on operating the 3RW5 HMI High Feature in the
Equipment Manual of the 3RW5 soft starter.
SIRIUS 3RW5 EtherNet/IP communication module
Manual, 05/2019, A5E45131885002A/RS-AA/001