9 Connecting the reader to SiPass integrated
9.1 Connecting the reader to SiPass integrated in OSDP mode
A
B
C
D
E
The connection between a reader and a Reader Interface Module (RIM) is as follows:
RIM (DRI/ERI)
12 V
0V
Tx/+
Rx/-
SiPass integrated can support both the VR and NGCR readers on the same OSDP bus.
© Siemens 2019
SiPass integrated RIM (DRI/ERI)
Power and A, B (OSDP)
Reader 1 (AR50M-MF Mullion reader with keypad)
Reader 2 (AR20M-MF Mullion reader)
Reader 3 (VR40S-MF MIFARE Reader with keypad and display)
27
VRxx-MF
+
-
A
B
A-100417-b
15.04.2019