Probe Mounting (Wall / Duct Version); Mounting Remote Sensing Probe Of Ee310-T5 - E+E Elektronik EE310 Operation Manual

Humidity/temperature transmitter
Hide thumbs Also See for EE310:
Table of Contents

Advertisement

4.3

Probe mounting (wall / duct version)

Fig. 7
Mounting of model EE310-T1. The probe
shall point downwards.
4.4

Mounting remote sensing probe of EE310-T5

For mounting the probe into a separation wall use the stainless steel mounting flange. The immersion
depth is adjustable. The probe shall be mounted horizontally.
temperature gradient along
the probe shall be avoided
probe into separation wall
Fig. 9
Mounting the remote probe of EE310-T5
For accurate measurement it is of paramount importance to avoid T gradients along the probe. In case
of large T difference between the front and the back of the probe, it is highly recommended to insert the
probe completely into the process. Should this not be possible, place a thermal isolation layer on the
part of the probe outside the process (on the cable side).
The stainless steel mounting flange is not appropriate for pressure tight mounting. For pressure tight
requirements use EE310-T10.
For probe hanging onto its cable from the ceiling in applications where condensation is likely to happen
it is important to avoid condense water getting from the cable to the probe and into the sensing head.
For this use the drip water protection, see chapter 8.
Operating instructions for EE310 Humidity / Temperature Transmitter
Fig. 8
bow for draining
condense water
Mounting of model EE310-T2. The probe
shall be mounted horizontally or vertically
pointing downwards.
sealing
drip water
protection
85
3.3"
hanging probe
13