Installation of the probe (see Fig. 11)
• Install the probe into the ball valve while the ball valve is closed.
• Open the ball valve.
• Slide the probe through the ball valve to the desired immersion depth. Depending on the process
pressure additional tools may be necessary for pushing the probe into the process. Make sure not to
damage the probe and the cable.
• Tighten the lock nut with a torque of 30 Nm.
Observe strictly the tightening torque. A torque lower than 30 Nm results a smaller retention force of the
clamping sleeve. This leads the risk of sudden expulsion of the sensing probe due to the pressure. A
torque higher than 30 Nm may lead to permanent deformation of the clamping sleeve and the sensing
probe. This would make the removal and re-installation of the probe difficult or even impossible.
metal sealing ring
(as a standard contained
with the probe)
extension
(is not available for
an NPT thread)
Fig. 11
Installation of the probe by utilizing the ball valve set
Removing the probe
• Hold firmly the probe to avoid it being suddenly expulsed when releasing the lock. Do not bend dam-
age the probe cable.
• Loosen slowly the lock nut with a spanner (spanner width 24) only till the probe is pushed out by the
overpressure in the process. Do not completely loosen the lock nut, but only as much as necessary
for the probe to slide.
• After the probe has been pushed out of the process up to the stop, close the ball valve.
• Remove the probe from the ball valve.
Observe the correct positioning of the sealing element 1 before reinstalling the probe.
Operating instructions for EE310 Humidity / Temperature Transmitter
metal sealing ring
(as a standard contained
with the ball valve set)
1/2" ball valve
adapter body
inside diameter
≥ 13.1 mm
(0.55")
lock nut
clamping sleeve
sealing element 2
sealing element 1
15