6 COMMUNICATIONS
Modbus Implementation: Preset Single Register
MM2 Implementation: Store Single Setpoint
This command allows the master to store a single setpoint into the memory of a MM2. The slave
response to this function code is to echo the entire master transmission.
For example, request slave 17 to store the value 01F4 in setpoint address 1020. After the transmis-
sion in this example is complete, setpoints address 1020 will contain the value 01F4. The master/
slave packet format is shown below:
Table 6–5: MASTER/SLAVE PACKET FORMAT FOR FUNCTION CODE 06H
MASTER TRANSMISSION
SLAVE ADDRESS
FUNCTION CODE
DATA STARTING ADDRESS
DATA
CRC
SLAVE RESPONSE
SLAVE ADDRESS
FUNCTION CODE
DATA STARTING ADDRESS
DATA
CRC
GE Power Management
BYTES
EXAMPLE
1
11
1
06
2
10 20
2
01 F4
2
8E 47
BYTES
EXAMPLE
1
11
1
06
2
10 20
2
01 F4
2
8E 47
MM2 Motor Manager 2
6.2 MODBUS FUNCTIONS

6.2.5 FUNCTION CODE 06H

DESCRIPTION
message for slave 17
store single setpoint
setpoint address 1020
data for setpoint address 1020
CRC error code
DESCRIPTION
message from slave 17
store single setpoint
setpoint address 1020
data stored in setpoint address 1020
CRC error code