4.4 S3 PROCESS
4.4 S3 PROCESS
This page is used to enter all process information. Setpoints Page 3 is divided into four sections,
PROGRAMMABLE INPUTS, INTERLOCK NAMES, FIELD STOP and ANALOG INPUT.
PATH: SETPOINTS MMM S3: PROCESS M PROGRAMMABLE INPUTS
The first five messages are repeated for all ten interlock outputs.
NOTE
INTERLOCK INPUT 1:
NOT USED
4
STARTUP OVERRIDE
DELAY:
0 s
RUNNING OVERRIDE
DELAY:
0 s
OPERATION:
INTERLOCK STOP
INSTANTANEOUS ALARM:
DISABLE
IL1 SWITCH TYPE:
N.O.
LOCAL ISOLATOR:
DISABLE
4-20
Range: NOT USED, PROCESS INTERLOCK A to PROCESS INTER-
LOCK J, PLANT INTERLOCK, LOCKOUT RESET, SETPOINT
ACCESS, AUTO PERMISSIVE, AUTO START A, AUTO START B,
RESET EMERGENCY STOP TRIP, RESET UNDERCURRENT TRIP,
TWO WIRE CONTROL, TEST SWITCH, REMOTE PERMISSIVE,
COMMUNICATIONS SELECT, INTERLOCK COUNTER, AUX RELAY
1 INHIBIT, WYE-DELTA 1M CONTACT, WYE-DELTA 2S CONTACT, U/
V RESTART INHIBIT, AUTOTRANS 2S CONTACT, STOP A, STOP B,
REMOTE RESET, MOTOR SELECTOR A/B, DUTY SELECT MAN-
UAL/AUTO, BYPASS CONTACT
Note that interlock input functions are active when the applicable switch
input is closed and energized. See the following page for explanation of
the range options.
Range: 0 to 3600 seconds or OFF; Step: 1 second
See PROCESS INTERLOCK A.
Range: 0 to 3600 seconds or OFF; Step: 1 second
See PROCESS INTERLOCK A.
Range: INTERLOCK STOP, LATCHED TRIP
See PROCESS INTERLOCK A.
Range: ENABLE, DISABLE
See PROCESS INTERLOCK A.
Range: N.O., N.C.
This setpoint allows the user to configure the type of switch used for the
programmable switch inputs as normally open (N.O.) or normally closed
(N.C.). When set to N.O. (factory default), if the switch input is closed, it is
in the 'healthy' position; if the switch is open, it is in the 'unhealthy' posi-
tion. When set to N.C., if the switch input is open, it is in the 'healthy'
position; if it is closed, it is in the 'unhealthy' position.
Range: ENABLE, DISABLE
The Local Isolator switch input can be enabled or disabled using this
Setpoint. When set to ENABLE a Local Isolator Trip will occur whenever
the Local Isolator switch input is open. The trip will automatically reset
when the switch input is closed.
MM2 Motor Manager 2
4 SETPOINTS
4.4.1 DESCRIPTION
4.4.2 PROGRAMMABLE INPUTS
GE Power Management