Nema Compatible Overload Curves - GE MOTOR MANAGER 2 Instruction Manual

Hide thumbs Also See for MOTOR MANAGER 2:
Table of Contents

Advertisement

4.3 S2 PROTECTION
Table 4–2: NEMA COMPATIBLE OVERLOAD CURVE TRIP TIMES (IN SECONDS)
OVERLOAD
LEVEL
1.05
1.10
1.20
1.30
1.40
1.50
1.75
4
2.00
2.25
2.50
2.75
3.00
3.50
4.00
4.50
5.00
5.50
6.00
6.50
7.00
7.50
8.00
The NEMA compatible overload curves are shown in the following chart. Note that K+E 11" x 17" for-
mat of time/overcurrent curves are available from factory upon request.
4-10
CLASS 10
CLASS 15
3349
5024
1635
2452
780
1170
497
746
358
536
275
412
166
250
114
172
84
127
65
98
52
78
43
64
30
46
23
34
17.8
27
14.3
21
11.7
17.6
9.8
14.7
8.3
12.4
7.1
10.7
6.2
9.3
5.4
8.1
MM2 Motor Manager 2

4.3.3 NEMA COMPATIBLE OVERLOAD CURVES

CURVE
CLASS 20
CLASS 30
6698
10047
3269
1560
995
715
549
333
229
169
131
105
86
61
46
36
29
23
19.6
16.6
14.3
12.4
10.9
4 SETPOINTS
4904
2340
1492
1073
824
499
343
253
196
157
129
91
67
53
43
35
29.4
24.9
21.4
18.6
16.3
GE Power Management