9 STARTER TYPES

9.6 INVERTER STARTER

When the RUN contact closes the inverter ramps up the motor to the programmed speed. When the
RUN contact opens, the inverter ramps down the motor to a stop.
To program the MM2 for inverter starter, set:
S1 CONFIGURATION\STARTER\STARTER TYPE: INVERTER
S1 CONFIGURATION\STARTER\RAMP UP TIME: 1 to 125 sec.
S1 CONFIGURATION\STARTER\RAMP DOWN TIME: 1 to 125 sec.
The RAMP UP TIME and RAMP DOWN TIME setpoints appear when the STARTER TYPE is selected as
INVERTER. See the next section for details on functionality.
GE Power Management
Figure 9–13: ELEMENTARY INVERTER STARTER
MM2 Motor Manager 2
9.6 INVERTER STARTER

9.6.1 DESCRIPTION

9
9-17