6.2 MODBUS FUNCTIONS
Modbus Implementation: Force Single Coil
MM2 Implementation: Execute Operation
This function code allows the master to request a MM2 to perform specific command operations. The
commands supported by the MM2 are listed in Section 6.4: APPLICATIONS on page 6–14.
For example, to request slave 17 to execute operation code 1 (reset), we have the following master/
slave packet format:
Table 6–4: MASTER/SLAVE PACKET FORMAT FOR FUNCTION CODE 05H
MASTER TRANSMISSION
SLAVE ADDRESS
FUNCTION CODE
OPERATION CODE
CODE VALUE
CRC
SLAVE RESPONSE
SLAVE ADDRESS
FUNCTION CODE
OPERATION CODE
6
CODE VALUE
CRC
The commands that can be performed by the MM2 using function code 05 can also be initiated by
using function code 10.
See Section 6.2.8: FUNCTION CODE 10H on page 6–12 for an example of performing commands
using function code 10.
6-8
BYTES
EXAMPLE
1
11
1
05
2
00 01
2
FF 00
2
DF 6A
BYTES
EXAMPLE
1
11
1
05
2
00 01
2
FF 00
2
DF 6A
MM2 Motor Manager 2
6 COMMUNICATIONS

6.2.4 FUNCTION CODE 05H

DESCRIPTION
message for slave 17
execute operation
operation code 1
perform function
CRC error code
DESCRIPTION
message from slave 17
execute operation
operation code 1
perform function
CRC error code
GE Power Management