How To Isolate A Device Across A Network System - EMS FirePoint 5000 Step-By-Step Manual

Hide thumbs Also See for FirePoint 5000:
Table of Contents

Advertisement

EMS 5000 FIREPOINT
8
Press  key one time and the screen will
display:
9
Press Yes key twice and the screen will now
display:
10
Press No key three times and the screen will
now display:
11
Turn the Control key switch to the off
Position and the screen will now display:
Note: The isolate LED on the 5000 FirePoint Panel will clear and the
isolate beep will stop.

6. How To Isolate A Device Across A Network System

To isolate a device across the network on the 5000 FirePoint, insert the key
into the panel controls keyswitch, located at the right of the panel.
Step
No
1
Turn the key to the on position and the
screen will display:
2
Press 0 key and the screen will now display:
3
Press  key three times and the screen will
display:
4
Press Yes key and the screen will now
display:
5
Press  key one time and the screen will
display:
©2015 EMS Security Group Ltd. All rights reserved.
Action
9
|Number is: 125
>Status is: ISOLATE<
| Zone is
Yes= Select
|Number is: 125
>Status is : ACTIVE <
| Zone is
Yes= Select
Panel in Access
Date
Status Normal
Date
Screen Display
Panel in Access
Date
|***Options ****|
>Passwords
|Time and Date |
Yes =Select
|
Logging
>Fire System Opts<
|Remote Access
Yes = select
|** Fire system **|
>Dev. Isolate/Test<
| Net. Isolate/Test |
Yes= Select
|Dev. Isolate/Test |
>Net. Isolate/Test <
|Zone Isolate/Test |
Yes= Select
TSD258 Iss 3 25/06/15 AJM
|
: 01
|
Time
|
: 01
|
Time
Time
Time
Time
<
Time
|
|
Time
Time
Time