How To Take Zones Out Of Test - EMS FirePoint 5000 Step-By-Step Manual

Hide thumbs Also See for FirePoint 5000:
Table of Contents

Advertisement

EMS 5000 FIREPOINT

12. How To Take Zones Out Of Test

To take zones out of test and back into original state i.e. all on the 5000
FirePoint. Insert the key into the panel controls keyswitch, located at the right
of the panel. Turn the key to the on position.
Step
No
1
Turn the key to the on position and the
screen will display:
2
Press 0 key and the screen will now display:
3
Press Yes key and the screen will now display:
4
Press Yes key and the screen will now display:
5
Enter 221100 and press the Yes key and the
screen will now display:
6
Press Any key and the screen will now
display:
7
Press  key three times and the screen
will now display:
8
Press Yes key and the screen will now
display:
9
Press  key twice and the screen will now
display:
©2015 EMS Security Group Ltd. All rights reserved.
Action
22
Screen Display
Panel in Access
Date
|***Options ****|
>Passwords
|Time and Date |
Yes =Select
|*PIN's and ACCESS*|
>User Log ON
|View Users
Yes =Select
Enter Your PIN
To Log On > _
Then Press YES
*******************
* Welcome Engineer *
********************
Push Any Key
|***Options ****|
>Passwords
|Time and Date |
Yes =Select
|Logging
>Fire System Opts<
| Remote Access |
Yes= Select
|** Fire system **|
>Dev. Isolate/Test<
| Net. Isolate/Test |
Yes= Select
|Net. Isolate/Test
>Zone. Isolate/Test <
|Brigade Isolate
Yes= Select
TSD258 Iss 3 25/06/15 AJM