Test Run - York HIDS006B21S Service Manual

Inverter-driven multi-split system heat pump air conditioners
Table of Contents

Advertisement

TROUBLESHOOTING

3.4 Test Run

Turn OFF all the power supply switches.
Use a tester and make sure that all the switches are turned OFF.
Before the test run, check that the unit is appropriately installed according to the Installation and Maintenance
Manual. After that, inspect the following items.
Check Item
1
Damage
2
Fan Motor
3
Fasteners
4
Refrigerant Leaks
5
DSW Setting
1
6
Insulation
7
Stop Valve Fully Open
8
Power Supply Phase
9
Turn ON Crankcase
2
Heater
10
Indoor and Outdoor
Temperature
1: Insulation Resistance
l If the unit has been turned OFF for long periods, insulation resistance may decrease to 1MW or less because
the refrigerant is retained in the compressor. Check the following points.
(a) Disconnect the cables of the compressor and measure the insulation resistance of the compressor itself.
If the resistance is 1MW or less, an insulation failure of another electrical charge part has occurred.
(b) If the resistance is 1MW or less, reconnect the compressor and turn ON the main power supply.
The compressor warms up automatically. Check the insulation resistance again after applying current for at
least three hours. (Preheating time depends on the air condition, piping length or refrigerant condition.)
l Before the leakage breaker is activated, check the rated capacity.
2: Stoppage of Compressor Operation
The compressor may NOT be operational for a maximum of four hours if the power supply is NOT turned ON in
advance.
At this time, the stoppage Code (d1-22) is displayed on the LCD of wired controller and the forced Thermo-OFF
function starts.
If operation of the compressor is necessary, turn ON the power supply of the outdoor unit, wait for 30 seconds
and press PSW5 on the outdoor unit PCB for at least three seconds. The forced Thermo-OFF function (d1-22)
is canceled and the compressor operation is available.
3: Working Range
Refer to "Page i" of Installation for details.
NOTE:
Thermo-ON: The outdoor unit and some indoor units are running.
Thermo-OFF: The outdoor unit and some indoor units stay on, but don't run.
3-48
Are the unit appearance and inside of the unit damaged?
Is the fan motor runner installed in the center of the casing?
Is the fan motor installed away from the casing?
(The fan motor should NOT be touched by the casing.)
Are the screws loose due to vibration during transportation?
Check that the fasteners are secured firmly during installation, especially for electrical
wiring.
Check that there are NO refrigerant leaks.
The tightening part of the pipe (flare part) may be loose because of vibration during
transport.
Check that the DSW setting is the same as the factory setting. (Refer to Section 3.1.3.)
Measure resistance between electrical component terminal and ground with a tester.
It is normal if the resistance is 1MW and over.
If 1MW or less, do not perform the operation due to insulation failure of electrical parts.
Do NOT apply electricity to the terminal board of operating line. (Control PCB may be
damaged.)
Prior to test run, check that the stop valve of the outdoor unit is completely open.
The operation is NOT possible with the incorrect power phase order or lacking phase.
• Alarm "05" is indicated on the LCD of the wired controller.
• "05" is indicated on the 7-segment display of the outdoor unit.
Check the power supply phase according to the caution label attached close to the
outdoor unit terminal block or inside of the service cover.
After completion of item checks 1 to 8, turn ON the power supply of the outdoor unit.
Apply power to the outdoor unit(s) at least 12 hours prior to operation of the system for
preheating of the compressor oil..
<For Use in both Cooling and Heating Operation>
Are indoor and outdoor temperature out of the working range?
(Heating operation may not be operated due to the activation of the overload operation
prevention under the ambient temperature of 66
To perform the test run, set the test run mode with the wired controller.
Contents
o
o
F (19
C) or over.)
SM-18001-rev.1