York HIDS006B21S Service Manual page 82

Inverter-driven multi-split system heat pump air conditioners
Table of Contents

Advertisement

MAINTENANCE
(Ducted High Static Type)
B. Removing Fan and Fan Motor from Bottom Side (For All Models)
(1) Remove the electrical box cover according to Section 4.2.1.2 "Removing PCB".
(2) Disconnect the two connectors for the fan motor located on the PCB2. Then remove the wirings.
(3) Remove the lower M4 screws securing the inlet flange.
Qty. of Screws (A): One (For (H,Y)IDH018B21S)
(4) Remove the lower M4 screws securing the lower cover at the fan side. Then remove the lower cover.
Qty. of Screws (B): 10 (For (H,Y)IDH018B21S)
4-8
TURN OFF all POWER supply switches.
Three (For (H,Y)IDH024 - 030B21S)
Four (For (H,Y)IDH036, 048B21S)
12 (For (H,Y)IDH024 - 048B21S)
M4 Screws (x (B))
Lower Cover
Tool
Phillips Screwdriver
Inlet Flange
M4 Screws (x (A))
Tool
Phillips Screwdriver
SM-18001-rev.1