5.5.4
Comfort Function
Following functions are not available depending on connected outdoor unit.
(1) Quick Function
This function is used when decreasing/increasing the indoor temperature quickly.
This function operates as follows for 30 minutes from the operation start-up.
This function is only available when the operation mode is COOL or HEAT.
The unit starts each time in quick mode until the setting is canceled.
Setting Condition
Default Setting
COOL
Default Setting +20% Default Setting +20% Default Setting +200%
HEAT
Default Setting +20% Default Setting +20% Default Setting +50%
NOTES:
1. If this function is set, indoor fan speed is automatically controlled regardless fan speed setting from
wired controller. (If there is an upper/lower limit of airflow, do not use this function.)
In case of Ducted (EconoFresh), do not use this function. If it is used for Ducted (EconoFresh), the
thermal load of the room may significantly increase depending on the outdoor temperature conditions.
2. The upper limit and target frequency of the compressor are same as Function Setting "Hc" or "Hh".
3. This function may increase power consumption.
(2) Power Up Setting
If the cooling/heating capacity seems insufficient during the normal operation, set this function.
By setting this function, the target frequency and upper limit of the compressor are set higher as
follows.
Setting Condition
Compressor Frequency for Cooling Operation Compressor Frequency for Heating Operation
0 (Default Setting)
1
Default Setting +20% Default Setting +20%
2
3
Default Setting +20% Default Setting +20% Default Setting +20% Default Setting +20%
NOTE:
The upper limit and target frequency of the compressor are same as Function Setting "Hc" or "Hh".
SM-18001-rev.1
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
Compressor Frequency
Upper Limit
Target Frequency
-
Upper Limit
Target Frequency
-
-
Variation Width
-
-
Power Up Mode
Upper Limit
-
-
-
-
Default Setting +20% Default Setting +20%
Indoor Fan
-
Automatically
-
Target Frequency
-
-
5-41