Troubleshooting Procedures - York HIDS006B21S Service Manual

Inverter-driven multi-split system heat pump air conditioners
Table of Contents

Advertisement

3.2 Troubleshooting Procedures

l Alarm Code Indication of Wired Controller
< CIW01 >
(5)
(4)
Alarm Code:
MODEL : F .08
IDU : TIC4036B21S
ODU : TVAHR120B31S
(6)
Sel.
(7)
(*1): If two or more indoor units having trouble are connected to the wired controller, the indicated indoor
unit is selectable.
(*2): The initial of model names are indicated as "T". These "T" are replaced with "H", "Y" or "C".
(Except for the wall mount model.)
When there is a combination of outdoor units, ODU indication is the model of the main outdoor unit
(Unit A).
(*3): The model names are not indicated depending on the unit type.
l The alarm code is indicated by the LED on the change-over box PCB.
LED4
LED5
LED6
LED7
LED
4
5
6
X
X
X
X
: Flashing (Turn ON; 0.5 sec./Turn OFF; 0.5 sec.), X: Turn OFF.
SM-18001-rev.1
(1) (2)
01-02
23
(3)
AlarmRst
Address
OP MODE
OK
Entr
< PCB of Change-Over Box >
Alarm
Code
7
X
03
Abnormal communication between change-over box and outdoor unit.
03
Abnormal communication between change-over box and indoor unit.
Two or more change-over boxes are connected between outdoor unit
C1
and indoor unit.
X
C2
Nine or more indoor units are connected to change-over box.
X
C3
The indoor units of different systems are connected to change-over box.
(1) Refrigerant Cycle No. (*1)
(2) Indoor Unit No. (*1)
(3) Alarm Code
(4) Unit Model Code
(5) Total Number of Indoor Units in the Same System
as the Indoor Unit Having Trouble
(6) Indoor Unit Model (*2) (*3)
(7) Outdoor Unit Model (*2) (*3)
Contents
TROUBLESHOOTING
3-17