(5) After removing the lower cover, the fan assembly can be seen.
Remove the wiring for the motor secured by the cable clamp of the fan mounting plate.
For (H,Y,C)IDS006 - 012B21S
(6) Remove eight M4 screws securing the casings onto the fan mounting plate and move the fan casings
slightly.
(7) Remove two M4 screws securing the motor holding bands to the motor base and remove the motor,
the fan casings and the fan runners at the same time.
ATTENTION:
The total weight of the fan motor, the fan casings and the fan runners is approximately
33 lbs. (15kg). Perform the above work carefully.
(8) Push the hooks at both sides of the fan casing and remove the lower part of the fan casing.
(9) Loosen the screws securing the fan motor and the fan runner using the hexagonal wrench (for M6
screw) and pull out to remove the fan runner.
Hook
SM-18001-rev.1
TURN OFF all POWER supply switches.
Motor Holding Band
M4 Screws (x 8)
Fan Casing
Tool
Phillips Screwdriver
M4 Screws (x 2)
Tool
Hexagonal Wrench
Hexagonal Wrench
Fan Runner
MAINTENANCE
(Ducted Slim Type)
Motor Shaft
4-31